The different HMI's


POL895 (Indoor Version) POL871 (Indoor/Outdoor Version)


The steps required


POL895 POL871

1) Press the Rotary Dial while "Password enter" is highlighted on the screen.


2) Rotate the Rotary Dial anti-clockwise to display the number 8 as the first digit of the code and then press the Rotary Dial to accept and move to the second digit.


3) Repeat #2 above until the code 8888 is displayed on the screen and then press the Rotary Dial to accept and login.

 

4) Rotate the Rotary Dial clockwise to highlight "System Overview" and then press the Rotary Dial to enter that menu.

 

5) Rotate the Rotary Dial clockwise to highlight "Communication" and then press the Rotary Dial to enter that menu.

 

6) Press the Rotary Dial while "Comm. Module Overview" is highlighted to enter that menu.

 

7) Rotate the Rotary Dial clockwise to highlight "Module # BACnet/IP" (Where # is the module number such as 1, 2 or 3) and then press the Rotary Dial to enter that menu.

 

8) Make any changes as required (NOTE: To end a line on the IP Address, Subnet Mask or Gateway use # as the last character).

 

9) Rotate the Rotary Dial clockwise to highlight "Write Settings" and then press the Rotary Dial to enter that menu.

 

10) Rotate the Rotary Dial clockwise to highlight "Active" and then press the Rotary Dial to accept.

 

11) Rotate the Rotary Dial clockwise to highlight "Reset Required!" and then press the Rotary Dial to enter that menu.

 

12) Rotate the Rotary Dial clockwise to highlight "Execute" and then press the Rotary Dial to accept and reboot the controller (Complete AHU) and when it restarts it will use the new settings.

1) Press the bottom right enter button while "Password enter" is highlighted on the screen.


2) Use the middle right down arrow button to display the number 8 as the first digit of the code and then press the bottom right enter button to accept and move to the second digit.


3) Repeat #2 above until the code 8888 is displayed on the screen and then press the bottom right enter button to accept and login.

 

4) Use the middle right down arrow button to highlight "System Overview" and then press the bottom right enter button to enter that menu.

 

5) Use the middle right down arrow button to highlight "Communication" and then press the bottom right enter button to enter that menu.

 

6) Press the bottom right enter button while "Comm. Module Overview" is highlighted to enter that menu.

 

7) Use the middle right down arrow button to highlight "Module # BACnet/IP" (Where # is the module number such as 1, 2 or 3) and then press the bottom right enter button to enter that menu.

 

8) Make any changes as required (NOTE: To end a line on the IP Address, Subnet Mask or Gateway use # as the last character).

 

9) Use the middle right down arrow button to highlight "Write Settings" and then press the bottom right enter button to enter that menu.

 

10) Use the middle right down arrow button to highlight "Active" and then press the bottom right enter button to accept.

 

11) Use the middle right down arrow button to highlight "Reset Required!" and then press the bottom right enter button to enter that menu.

 

12) Use the middle right down arrow button to highlight "Execute" and then press the bottom right enter button to accept and reboot the controller (Complete AHU) and when it restarts it will use the new settings.